ISOMETER® iso685…

  • Predefined measurement profiles
  • Reliable measurement of insulation resistance, voltage, capacitance and frequency
  • Integrated web server
  • Modbus TCP/RTU
  • History memory

The ISOMETER® is an insulation monitoring device in accordance with IEC 61557-8 for IT systems. The devices are universally applicable in AC, 3(N)AC, AC/DC and DC systems. AC systems may include extensive DC-supplied loads (such as rectifiers, inverters, variablespeed drives).

Device variants
iso685-D: This device variant ISOMETER® iso685-D features a high-resolution graphic LC display and operating controls for direct operation of the device functions. It cannot be combined with an FP200.
iso685-S: This device variant ISOMETER® iso685-S features neither a display nor operating controls. It can only be used in combination with the FP200 and it is operated via this front panel.
Option "W": The ISOMETER®s with and without integrated display are available with option „W“ for extreme climatic and mechanical conditions (ISOMETER® iso685W-D and iso685W-S).

Questions? Contact us!

ISOMETER® iso685…
ISOMETER® iso685…
  • Predefined measurement profiles
  • Reliable measurement of insulation resistance, voltage, capacitance and frequency
  • Integrated web server
  • Modbus TCP/RTU
  • History memory

The ISOMETER® is an insulation monitoring device in accordance with IEC 61557-8 for IT systems. The devices are universally applicable in AC, 3(N)AC, AC/DC and DC systems. AC systems may include extensive DC-supplied loads (such as rectifiers, inverters, variablespeed drives).

Device variants
iso685-D: This device variant ISOMETER® iso685-D features a high-resolution graphic LC display and operating controls for direct operation of the device functions. It cannot be combined with an FP200.
iso685-S: This device variant ISOMETER® iso685-S features neither a display nor operating controls. It can only be used in combination with the FP200 and it is operated via this front panel.
Option "W": The ISOMETER®s with and without integrated display are available with option „W“ for extreme climatic and mechanical conditions (ISOMETER® iso685W-D and iso685W-S).

Questions? Contact us!

Features

  • ISOMETER® for IT AC systems with galvanically connected rectifiers or inverters and for IT DC systems (IT = unearthed systems)
  • Automatic adaptation to the existing system leakage capacitance
  • Combination of AMPPlusand other profilespecific measurement methods
  • Two separately adjustable response value ranges of 1 kΩ…10 MΩ
  • High-resolution graphical LC display
  • Connection monitoring (monitoring of the measuring lines)
  • Automatic device self test
  • Graphical representation of the insulation resistance over time (isoGraph)
  • History memory with real-time clock (buffer for three days) for storing 1023 alarm messages with date and time
  • Current or voltage output 0(4)…20 mA, 0…400 μA, 0…10 V, 2…10 V (galvanically separated), which is analogous to the measured insulation value of the system
  • Freely programmable digital inputs and outputs
  • Remote setting via the Internet or Intranet (Webserver/Option: COMTRAXX® Gateway)
  • Worldwide remote diagnosis via the Internet (made available by Bender Service only)
  • RS-485/BS (Bender sensor bus) for data exchange with other Bender devices 
  • BCOM, Modbus TCP/RTU and web server 
  • Voltage expandable via coupling devices

Applications

  • AC, DC or AC/DC main circuits
  • AC/DC main circuits with directly connected DC components, such as rectifiers, converters, variable-speed drives
  • UPS systems, battery systems
  • Heaters with phase control
  • Systems including switched-mode power supplies
  • IT systems with high leakage capacitances

ISOMETER® iso685… Variant(s)

TypeNominal system voltage range UnSupply voltage USDisplayOption WArt. No.
iso685-DAC 0…690 V; 1…460 Hz /
DC 0…1000 V
AC 24…240 V; 50…400 Hz /
DC 24…240 V
integratedB91067010
iso685W-DAC 0…690 V; 1…460 Hz /
DC 0…1000 V
AC 24…240 V; 50…400 Hz /
DC 24…240 V
integrated-40…+70°C,
3K23, 3M12
B91067010W
iso685-S + FP200AC 0…690 V; 1…460 Hz /
DC 0…1000 V
AC 24…240 V; 50…400 Hz /
DC 24…240 V
detachedB91067210
iso685W-S + FP200AC 0…690 V; 1…460 Hz /
DC 0…1000 V
AC 24…240 V; 50…400 Hz /
DC 24…240 V
detached-40…+70°C,
3K23, 3M12
B91067210W

Optional Accessories for ISOMETER® iso685…

Type designationTypeArt. No.
Coupling devicesAGH150W-4
AGH204S-4
AGH520S
AGH676S-4
B98018006
B914013
B913033
B913055

Possible measuring instruments on request!

Type designationArt. No.
A set of screw terminals*B91067901
A set of push-wire terminalsB91067902
Enclosure accessories (terminal cover, 2 mounting clips)*B91067903

* included in the scope of delivery

Downloads for ISOMETER® iso685…